Conversion kit
Lider Autotest



Technical profile:
- Power of fluorescent lamp: 6 - 80W
- Emergency operation time: 1, 2 or 3 hours
- Type of fluorescent lamp: T8, T5, compact lamps
- Ballast: KVG, EVG
Technical specification:
- Regular power supply: 220-240V/50-60Hz
- Fluorescent lamp power range 6-80W (depends on a model)
- Ambient temperature (ta): 0.. + 55°C.
- Operation temperature (te): 0.. + 70°C
- Batteries used: high temperature, non-maintained NiCd HT battery
- Battery package voltage: 3.6V; 4.8V; 6V and the capacity 1,0 - 4Ah (depends on the model)
- Rated current of battery discharge 0,1C
- Maximum current of battery discharge: <0,95C (emergency operation)
- Maximum charging time: 24h
- Emergency operation time: 1, 2, 3h
- Operation frequency: 25kHz - 30kHz
- The section of attached wires: 0,5 - 1,5 mm
Characteristics:
Test A is run automatically every 30 days.
Test A checks the following parameters:
- Enforcing emergency operation of the frame for 5 minutes
- Control of battery power discharge
- Control of minimum voltage of battery
Test B is run automatically every 360 days. Test B checks the following parameters:
- Enforcing emergency operation of the frame for all duration time (l,2,3h)
- Control of battery power discharge
- Control of minimum voltage of battery
Test signaling continues. After the 230V AC
power is on again the unit remains in emergency lighting mode until a full cycle of TEST A or B is completed.
Download:
| Name | Files |
|---|---|
| catalogue card | Lider AT EN.pdf |
Description:
| code | power |
operation time |
battery |
| LE/36/1/AT | 6W-36W | 1 h | Ni-Cd 3,6V 2,5Ah |
| LE/36/2/AT | 6W-36W | 2 h | Ni-Cd 3,6V 2,5Ah |
| LE/36/3/AT | 6W-36W | 3 h | Ni-Cd 3,6V 4,0Ah |
| LE/58/1/AT | 6W-58W | 1 h | Ni-Cd 4,8V 2,5Ah |
| LE/58/2/AT | 6W-58W | 2 h | Ni-Cd 4,8V 2,5Ah |
| LE/58/3/AT | 6W-58W | 3 h | Ni-Cd 4,8V 4,0Ah |
| LE/80/1/AT | 6W-80W | 1 h | Ni-Cd 6,0V 2,5Ah |
| LE/80/2/AT | 6W-80W | 2 h | Ni-Cd 6,0V 2,5Ah |
| LE/80/3/AT | 6W-80W | 3 h | Ni-Cd 6,0V 4,0Ah |